D400 GC (60 Hz) Generator Set
US
Metric
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
Minimum Rating
400 ekW
Maximum Rating
400 ekW
Emissions/Fuel Strategy
EPA Stationary Emergency
Voltage
480 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
Cat® C13 In-line 6, 4-cycle diesel
Bore
5.10 in
130.00 mm
Stroke
6.20 in
157.00 mm
Displacement
763.00 in³
12.50 B
Compression Ratio
16.3:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Fuel System
MEUI
Governor Type
ADEM™A4
Generator Set Dimensions
Length - Maximum
182.80 in
4625.00 mm
Width - Maximum
64.20 in
1630.00 mm
Height - Maximum
96.70 in
2456.00 mm
Height - Minimum
80.30 in
2039.00 mm
Dry Weight - Genset (minimum)
7330.40 lb
3325.00 kg
Dry Weight - Genset (maximum)
4107.00 lb
9054.40 kg
Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to104°F (40°C)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- ULC Certification Available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
- Air Inlet System
- Air cleaner - Non-Canister, Disposable
- Aftercooler core
- Turbocharger
- Control Panel
- GCCP 1.2
- Cooling System
- Blower fan and fan drive with guards
- Coolant drain valve.
- Radiator sight gauge
- Radiator, Package mounted.
- Jacket water pump, gear driven, centrifugal
- Thermostats and housing.
- Exhaust System
- Exhaust manifold; dry
- Fuel System
- Primary fuel filter w/integral water separator and secondary filter, spin on
- Engine fuel transfer pump
- Fuel cooler
- Fuel priming pump
- Integral Tank Base, 24 Hrs, UL142
- Generator Set
- All protective devices and control functions simulated and checked
- Complete system designed & built at ISO 9001:2000 certified facilities
- Factory tested to design specifications at full load conditions
- Generators and Generator Attachments
- Insulation, Class H
- IP23 protection
- Standard winding protection for non-harsh environments with relative humidity ? 95%
- 6 leads
- Terminal Box, IP22 RHS Facing, Bottom Cable Entry
- Easy access to AVR and terminals
- Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
- Voltage regulator (single phase sensing)
- Governing System
- Cat Electronic Governor (ADEM A4)
- Lube System
- Fumes disposal to front of radiator.
- Lubricating Oil, CK-4 (10W-30)
- Oil cooler
- Shallow oil pan.
- Oil filler and dipstick.
- Oil filter, spin on.
- Oil drain with valve.
- Mounting System
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provisions and termination points for coolant and lube oil drain lines
- Protection
- Safety Shutoff - Low Oil Pressure
- Safety Shutoff - High water temperature
- Safety Shutoff - Overspeed
- Starting/Charging System
- 24-volt electric starting motor.
- 24V,45 amp charging alternator.
- General
- Lifting Eyes
- Vibration damper.
- Parts Book
Optional Equipment
- Air Inlet System
- Air Cleaner (Non-Canister Disposable)
- Bases, Mounting & Fuel Tanks
- Audio & Visual Fuel Alarm (@90% Fuel Level)
- Integral Tank Base, 24 Hrs, UL142
- 5 gallon Spill Containment
- Fuel Tank Fill Pipe & Lockable Cap
- Overfill Prevention Valve
- Wide Base - Skid
- Circuit Breaker
- 1200A LSI
- 1200A LS/I
- 600A LS/I
- 400A LS/I
- 800A LS/I
- 600A LSI
- Auxiliary Contacts
- 800A LSI
- 400A LSI
- Control System
- Twist Release, Red Button Emergency Stop
- Ground Fault Relay
- Volt Free Contacts
- Audible Alarm Gp
- 16 -light NFPA 99/110 Annunciator
- 20A GFCI (Ground Fault Circuit Interrupter)
- 100A Load Center
- Product Link Remote Monitoring hardware
- Enclosures
- AC & DC Source Lights
- E-Stop
- Sound Attenuated Level 2 Enclosure (White)
- Exhaust System
- 8" Muffler - 25 dBA Attenuation
- Manifold & Turbocharger Guards
- Flexible Exhaust Connection
- Generator
- Space Heater
- Permanent Magnet Generator
- Circuit Breakers
- 4 Pole (IEC-100% rated) circuit breaker - Motorised
- Circuit breaker (IEC) auxiliary contacts
- Shunt trip for IEC circuit breaker
- Starting System
- Oversize Battery Set, 1400 CCA, 200 amp/hr.
- Standard Battery Set: 1000 CCA, 90 amp/hr.
- Jacket Water Heater
- Battery Charger (UL Certified)
- General
- Generator Test Report
- Extended Service Coverage
- UL2200 Certification
- CSA Certification
- starting / Charging System
- Jacket water heater
- Battery disconnect switch